Pengurangan saiz dan kenaikan eksponen dalam bilangan komponen elektronik
bersepadu akan meningkatkan kepadatan kuasa dan fluks haba litar. Bendalir nano
barium titanate (IV) telah dicadangkan untuk menggantikan cecair penyejukan
konvensional seperti air dan etilena glikol (EG). Bendalir nano barium titanate (IV)
disediakan dalam kepekatan volum 0.1 vol.%, 0.3 vol.% dan 0.5 vol.% dengan Gam
Arab (GA) sebagai surfaktan. Ciri-ciri termofizikal dikaji dengan bendalir nano dengan
dikenalkan 20 W, 40 W dan 60W dalam sistem paip gelung haba. Penambahan bendalir
nano barium titanate (IV) terbukti dapat meningkatkan pengaliran terma sehingga
maksimum 31.28% berbanding dengan air suling. Walau bagaimanapun, dari segi
nombor Nusselt (Nu), air suling menunjukkan keupayaan pemindahan haba lebih baik
daripada bendalir nano dengan perbezaan maksimum sebanyak 46.5%. Haba masuk
secara pengaliran lebih tinggi daripada haba keluar melalui perolakan telah
menyebabkan suhu permukaan sentuhan cecair menjadi lebih tinggi berbanding dengan
air suling dengan penggunaan bendalir nano. Oleh itu, kombinasi RAM blok air dengan
bendalir nano barium titanate (IV) tidak sesuai untuk aplikasi penyejukan elektronik.
_______________________________________________________________________________________________________
The reduction of size and the exponential increment in the number of integrated
electronic components have eventually increased the power density and heat flux of the
circuit. Barium titanate (IV) nanofluid has been proposed to replace the conventional
cooling fluid such as water and ethylene glycol (EG). Barium titanate (IV) nanofluid is
prepared at 0.1 vol.%, 0.3 vol.% and 0.5 vol.% with Arabic Gum (AG) as the surfactant.
The thermophysical properties are studied with the nanofluid under heat output of 20 W,
40 W and 60W in a closed loop fluid system. The addition of barium titanate (IV)
nanofluid is proven to improve the thermal conductivity by maximum of 31.28%
compared to distilled water at 0.5 vol.%. However, in term of Nusselt number (Nu),
distilled water shows superior heat transfer capability than nanofluids with maximum
difference of 46.5% with nanofluids. Lesser heat is convected out than the heat is
conducted into the RAM water block by nanofluid which causes fluid contact surface
temperature to be greater than the results from distilled water. Hence, the combination
of RAM water block and barium titanate (IV) nanofluid is not suitable for electronic
cooling application.